Three Phase LV Hybrid Inverter

| Model Name | HES(6K)LT | HES(8K)LT | HES(10K)LT | HES(12K)LT |
|---|---|---|---|---|
| AC Output (Off-grid Side) | ||||
| Rated Output Power | 6KW | 8KW | 10KW | 12KW |
| Max.Output Power | 6.6KVA | 8.8KVA | 11KVA | 13.2KVA |
| Peak Power&Duration | 20KVA(10s)* | |||
| Max.Output Current | 10A | 13.3A | 16A | 20A |
| Rated Output Voltage | 3/N/PE,220/380Vac,230/400Vac | |||
| Switching Time | <10ms | |||
| GEN Max.Current | 36.4A | |||
| GEN Voltage Range | 185-276V(P2N) | |||
| AC Output(Grid Side) | ||||
| Rated Output Power | 6KW | 8KW | 10KW | 12KW |
| Max.Output Power | 6.6KVA | 8.8KVA | 11KVA | 13.2KVA |
| Max.Output Current | 10A | 13.3A | 16A | 20A |
| AC Input(Grid Side) | ||||
| Max.Input Power | 24KVA | |||
| Rated Voltage | 3/N/PE,220/380Vac,230/400Vac | |||
| Grid Voltage range | 185-276V(P2N) | |||
| Grid Frequency | 50/60±5Hz | |||
| DC Input | ||||
| Max.Input Power | 18KW | |||
| Max.Input Voltage | 800V | |||
| Number of MPPT | 3 | |||
| Max.Input String Per MPPT | 2001/01/01 | |||
| MPPT Voltage Range | 130-800V | |||
| Starting Voltage | 140V | |||
| Max.Input Current | 20A/20A/20A | |||
| Short-Circuit Current | 24A24A/24A | |||
| Battery Parameter | ||||
| Battery Type | Lithium-ion/Lead-Acid/Sodium-ion | |||
| Number of Battery Input | 2 | |||
| Battery Voltage Range | 30-60V | |||
| Battery Charging/Discharging Current | 125A*2 | |||
| Efficiency | ||||
| Max.Efficiency | 98.2% | |||
| European Efficiency | 97.70% | |||
| Max.Battery Charging/ Discharging Efficiency |
95.00% | |||
| General Data | ||||
| Size(*H*D) | 465mm*665mm*165mm | |||
| Weight | 36kg | |||
| Noise | <45dB(A) | |||
| Operating Temperature | -25℃~+60°℃(>45℃ Derating) | |||
| Operating Altitude | 4000m(>3000m Derating) | |||
| Cooling Method | Intelligent Air Cooling | |||
| Ingress Protection Grade | IP65 | |||
| Topology | Isolation | |||
| Communication Port | LED/MIFI/4G/Bluetooth/RS485 | |||
| Protection | DC Switch;Reverse Polarity Protection;AC Overvoltage/Overcurrent/Short Circuit Protection; Anti-islanding Protection;Residual Current Monitoring;Insulation Resistance Detection; Surge Protection:DC Typel/AC Type IⅢ;AFCI(Optional);PID(Optional) |
|||
| Certification | ||||
| CE-LVD | IEC62109-1&2,IEC62477-1 | |||
| CE-EMC | EN61000-6-1,EN61000-6-2,EN61000-6-3,EN61000-6-4 EN 61000-4-16,EN 61000-4-18,EN 61000-4-29 |
|||
| Grid | VDE-AR-N 4105;VDE 0126-1-1 EN 50549-1;G98,G100;CEI 0-21;AS/NZS4777.2 NRS 097-2-1 | |||
*Overload output is dependent on sufficient PV and battery energy
We usually reply within 12 hours