Battery Storage for Peak Shaving and Demand Charge Management

What is battery peak shaving?

Peak shaving uses stored energy to supplement grid power during high-demand periods. For a business billed partly on measured maximum demand, this may lower the demand component of its electricity charges. The benefit depends on the actual tariff, metering interval, recurring load peaks and how the battery is controlled; it is not an automatic saving.

Size the battery for the shape of the peak

Start by plotting measured facility demand over the billing period. Set a proposed import limit and identify how far, and for how long, demand exceeds it. For example, a hypothetical 180 kW load with a 130 kW import target requires 50 kW of battery discharge. If that difference persists for two hours, 100 kWh must be delivered, before system losses and reserves.

A short, steep peak may need a high PCS power rating with relatively little energy. A longer production shift may require more storage capacity. Check the charging window: charging during an expensive or already busy period can offset the intended savings.

Configure the EMS around the tariff

The energy management system should monitor import at the point relevant to billing, control discharge and respect state-of-charge limits. Evaluate different target thresholds against historical load data and check how the strategy behaves on unusually busy days. If solar is installed, consider forecasting generation and retaining enough storage for later peaks.

For facilities that also require backup, distinguish the backup reserve from energy allocated to reducing demand. Check whether the selected system supports the necessary operating modes and grid connection conditions.

Evaluate the economics

Compare the baseline bill with simulated dispatch under the actual tariff. Include the frequency of peaks, any demand ratchet rules, energy prices, round-trip losses, maintenance and potential replacement costs. Verify results with measured post-installation data. Avoid using a fixed savings percentage from an unrelated project.

Explore configurations

YIY's commercial and industrial on-grid BESS solution is intended for grid-connected demand management. Compare the on-grid commercial battery storage range and project cases to understand the available power and capacity combinations. Provide interval load data and the electricity bill for project-specific evaluation.